3: Transformer Action
3: Transformer Action
Transformer action depends upon magnetic lines of force (flux)mentioned above.
At the instant a transformer primary is energized with AC, a flow of electrons (current) begins.
During the instant of switch closing, buildup of current and magnetic field occurs.
As current begins the positive portion of the sine wave, lines of magnetic force (flux) develop outward from the coil and continue to expand until the current is at its positive peak.
The magnetic field is also at its positive peak.
The current sine wave then begins to decrease, crosses zero, and goes negative until it reaches its negative peak.
The magnetic flux switches direction and also reaches its peak in the opposite direction.
With an AC power circuit, the current changes (alternates) continually 60 times per second, which is standard in the United States. Other countries may use other frequencies.
In Europe, 50 cycles per second is common.
Strength of a magnetic field depends on the amount of current and number of turns in the winding.
When current is reduced, the magnetic field shrinks.
When the current is switched off, the magnetic field collapses.
When a coil is placed in an AC circuit, as shown in figure , current in the primary coil will be accompanied by a constantly rising and collapsing magnetic field.
When another coil is placed within the alternating magnetic field of the first coil, the rising and collapsing flux will induce voltage in the second coil.
When an external circuit is connected to the second coil, the induced voltage in the coil will cause a current in the second coil.
The coils are said to be magnetically coupled; they are, however, electrically isolated from each other.
Many transformers have separate coils, as shown in figure , and contain many turns of wire and a magnetic core, which forms a path for for and concentrates the magnetic flux. The winding receiving electrical energy from the source is called the primary winding.
The winding which receives energy from the primary winding, via the magnetic field, is called the “secondary” winding.
Either the high- or low-voltage winding can be the primary or the secondary.
With GSUs at Reclamation powerplants, the primary winding is the low-voltage side (generator voltage), and the high voltage side is the secondary winding (transmission voltage).
Where power is used (i.e., at residences or businesses), the primary winding is the high-voltage side, and the secondary winding is the low-voltage Side.
Comments
Post a Comment